Skip to content
Blog

Danfoss · AK-SM 800A · CISA KEV

Danfoss AK-SM 800A: Three Old System Manager Flaws Added to CISA KEV

CVE-2023-25915 (9.9 per DIVD), CVE-2023-25914 and CVE-2025-41450: three Danfoss AK-SM 800A flaws added to CISA KEV on November 25. Versions and fixes.

On November 25, 2026, CISA added three vulnerabilities in the Danfoss AK-SM 800A series to the KEV catalog. None of them is new: two date back to August 2023, the third to May 2025. Their KEV listing means exploitation has now been observed.

The AK-SM 800A is a Danfoss system manager, a building and equipment controller found in retail stores. The KEV entry hints at it: one of the flaws exposes store names along with internal IP addresses and usernames.

It's exactly the kind of device that slips past IT's inventory: installed by a contractor, rarely updated, sometimes reachable remotely for maintenance.


The Three Vulnerabilities

CVEType (CWE)CVSS 3.1 (CNA)CVSS 3.1 (NVD)NVD publicationCISA deadline
CVE-2023-25915Improper input validation (CWE-20)9.9 (DIVD)8.82023-08-212026-11-28
CVE-2023-25914Path traversal (CWE-22)8.8 (DIVD)8.82023-08-212026-11-28
CVE-2025-41450Improper authentication (CWE-305)8.27.52025-05-082026-12-09

Published vectors:

  • CVE-2023-25915: DIVD CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H, NVD CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
  • CVE-2023-25914: DIVD and NVD CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
  • CVE-2025-41450: CNA CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:L/A:H, NVD CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

The two 2023 flaws were reported by the DIVD CSIRT (case DIVD-2023-00025), which is also the CNA that assigned them.


What NVD Describes

CVE-2023-25915: insufficient input validation lets an authenticated remote attacker execute arbitrary commands on the system. DIVD scores it 9.9 with a scope change (S:C); NVD settles on 8.8.

CVE-2023-25914: improper restriction lets an authenticated attacker read system files through the XML interface. NVD notes that what can be read may lead to full system compromise.

CVE-2025-41450: improper authentication (CWE-305, bypass through an alternate path or channel). NVD's description is a single line; CISA is more specific: an attacker can generate a web report exposing sensitive information, including internal IP addresses, usernames and store names. The CNA and NVD disagree sharply on the vector: the former assumes high complexity and user interaction, NVD a simple attack with no interaction.

Why the three together

Both 2023 flaws need an account (PR:L). The 2025 one doesn't (PR:N) and hands out usernames. NVD doesn't describe a chain, but it's plausible that a campaign pairs the 2025 information leak with authenticated access to reach command execution or file reads. That's an inference, not a published fact.

NVD's references for CVE-2025-41450 include a GitHub repository named "fromagegate"; NVD doesn't describe its contents.


Affected Versions

CVEAffected versions (NVD)First version out of range
CVE-2023-25915AK-SM 800A firmware up to and including 3.3not stated by NVD
CVE-2023-25914AK-SM 800A firmware up to and including 3.3not stated by NVD
CVE-2025-41450AK-SM 8xxA firmware before 4.24.2

These numbers are bounds from NVD's CPE configuration, not necessarily the version to install. For the 2023 flaws, NVD stops at "up to and including 3.3" with no fixed version: the reference is Danfoss advisory DSA-2023-08-01. For CVE-2025-41450, it's DSA-2025-03-01. Firmware outside both ranges should cover all three flaws, but confirm the recommended version in the advisories before scheduling the work.


Detection

  • Exposure: is the system manager reachable from the Internet, or from a contractor network? That's the first question, and often the most useful one
  • Web reports generated recently with no known request behind them (CVE-2025-41450)
  • Requests to the XML interface containing path traversal sequences (../) or system file names (CVE-2023-25914)
  • Authenticated logins from unusual addresses, with rarely used accounts
  • Configuration changes or abnormal behavior of the equipment the system manager controls

The KEV entry points to BOD 26-04 and its forensic triage requirements.


Mitigation

1. Update the firmware

Following advisories DSA-2023-08-01 and DSA-2025-03-01. The CISA deadline is November 28 for the two 2023 flaws, December 9 for CVE-2025-41450.

2. Take the system manager off the Internet

Building and equipment controllers shouldn't be exposed. Maintenance access should go through a VPN or a controlled remote access solution, never an open port.

3. Change credentials

Two of the three flaws need an account, and the third leaks usernames: replace default or shared passwords, and remove contractor accounts that are no longer used.

4. Isolate the operational network

Put the system manager in a segment separate from the office and point-of-sale networks, with flows limited to what's strictly needed.


Why Continuous Monitoring of Your Operational Equipment Matters

A 2023 flaw entering KEV in late 2026 is a sign that a fleet of devices went three years without updates, and someone noticed. Building and equipment controllers rarely make it into IT's inventory, and that's precisely why they stay vulnerable.

With cveo.tech, add your system managers and controllers to your inventory with their firmware version, and get an automatic alert whenever a CVE affecting them is published or enters the CISA KEV catalog, even years after publication.

Know which CVEs hit the versions you run.

Add the product and its version: cveo.tech lists the CVEs that affect it right away, then alerts you by email when a new one affects it — including before NVD has finished its analysis. Free, an account is all it takes.

Every Monday

The week's critical CVEs, in your inbox

One email a week: the CVSS ≥ 9 vulnerabilities published in the last seven days, plus our latest analyses. Nothing else.

Double opt-in by email. Unsubscribe in one click, any time.